1. Error number (D806*): 0000

Error message: NOERROR--No abnormal error occurred

Exception content and reason: no abnormality occurred

Countermeasure: Please check if the connection between the host and the I/O expansion base/module is normal.

2, the error number (D8061): 6101

Error message: PLCHARDWAREERROR (PLC hardware failure)

Abnormal content: PLC stops running

Exception content and reason: RAM error

Countermeasure: Please check if the connection between the host and the I/O expansion base/module is normal.

3, the error number (D8061): 6102

Error message: PLCHARDWAREERROR (PLC hardware failure)

Abnormal content: PLC stops running

Abnormal cause: loop error

Countermeasure: Please check if the connection between the host and the I/O expansion base/module is normal.

4, the error number (D8061): 6103

Error message: PLCHARDWAREERROR (PLC hardware failure)

Abnormal content: PLC stops running

Exception content and cause: I/OBus error, must be driven first to drive M8069=ON

Countermeasure: Please check if the connection between the host and the I/O expansion base/module is normal.

5, the error number (D8061): 6104

Error message: PLCHARDWAREERROR (PLC hardware failure)

Abnormal content: PLC stops running

Abnormal cause: I/O expansion base 24V is abnormal, it must be driven first to drive M8069=ON

Countermeasure: Please check if the connection between the host and the I/O expansion base/module is normal.

6, error number (D8061): 6105

Error message: PLCHARDWAREERROR (PLC hardware failure)

Abnormal content: PLC stops running

Abnormal cause: the watchdog timer is abnormal

Countermeasure: Please check if the connection between the host and the I/O expansion base/module is normal.

7, error number (D8062): 6201

Error message: PLC/PPCOMMUNICATI (PLC/writer communication error)

Error content: Parity/f rameError

Countermeasures: Please check if the connection between the host and the 20P or PC is normal.

8, error number (D8062): 6202

Error message: PLC/PPCOMMUNICATI (PLC/writer communication error)

Error content: Communication word is abnormal

Countermeasures: Please check if the connection between the host and the 20P or PC is normal.

9, error number (D8062): 6203

Error message: PLC/PPCOMMUNICATI (PLC/writer communication error)

Wrong content: Inconsistent inspection of communication data

Countermeasures: Please check if the connection between the host and the 20P or PC is normal.

10. Error number (D8062): 6204

Error message: PLC/PPCOMMUNICATI (PLC/writer communication error)

Error content: Communication string is abnormal

Countermeasures: Please check if the connection between the host and the 20P or PC is normal.

11, error number (D8062): 6205

Error message: PLC/PPCOMMUNICATI (PLC/writer communication error)

Error content: Communication command is abnormal

Countermeasures: Please check if the connection between the host and the 20P or PC is normal.

12, the error number (D8063): 6301

Error message: PARALLELl inkERROR (parallel operation communication error)

Error content: Parity/f rameError

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

13, error number (D8063): 6302

Error message: PARALLELl inkERROR (parallel operation communication error)

Error content: Communication word is abnormal

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

14, error number (D8063): 6303

Error message: PARALLELl inkERROR (parallel operation communication error)

Wrong content: Inconsistent inspection of communication data

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

15, error number (D8063): 6304

Error message: PARALLELl inkERROR (parallel operation communication error)

Error content: Communication string is abnormal

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

16, error number (D8063): 6305

Error message: PARALLELl inkERROR (parallel operation communication error)

Error content: Communication command is abnormal

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

17, error number (D8063): 6306

Error message: PARALLELl inkERROR (parallel operation communication error)

Error content: exceed monitoring time

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

18, the error number (D8063): 6312

Error message: PARALLELl inkERROR (parallel operation communication error)

Error content: Parallel operation error

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

19. Error number (D8063): 6313

Error message: PARALLELl inkERROR (parallel operation communication error)

Wrong content: Parallel operation summary check is inconsistent

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

20, the error number (D8063): 6314

Error message: PARALLELl inkERROR (parallel operation communication error)

Error content: Parallel operation string exception

Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.

21, the error number (D8064): 6401

Error message: PARAMETERERROR (parameter error)

Error content: program summary check is inconsistent

Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.

22, the error number (D8064): 6402

Error message: PARAMETERERROR (parameter error)

Wrong content: Memory capacity setting is incorrect

Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.

23, the error number (D8064): 6403

Error message: PARAMETERERROR (parameter error)

Wrong content: Power failure hold area setting is incorrect

Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.

24, the error number (D8064): 6404

Error message: PARAMETERERROR (parameter error)

Error content: The annotation area setting is incorrect

Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.

25, the error number (D8064): 6405

Error message: PARAMETERERROR (parameter error)

Error content: The file buffer area setting is incorrect

Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.

26, the error number (D8064): 6409

Error message: PARAMETERERROR (parameter error)

Error content: Other settings are incorrect

Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.

27, the error number (D8065): 6501

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content: The combination of instruction and operand is incorrect

Countermeasure: Please check if each instruction in the program is used correctly.

28, the error number (D8065): 6502

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content: There is no OUTT before the set value, OUTC command

Countermeasure: Please check if each instruction in the program is used correctly.

29, error number (D8065): 6503

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content: OUTT, there is no set value after OUTC, and the number of operands of the application instruction is insufficient.

Countermeasure: Please check if each instruction in the program is used correctly.

30, the error number (D8065): 6504

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content: Repeat the use of the number of P, interrupt the insertion of the input number and repeat the use of the high-speed counter input number

Countermeasure: Please check if each instruction in the program is used correctly.

31. Error number (D8065): 6505

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content: The specified component is out of range

Countermeasure: Please check if each instruction in the program is used correctly.

32, error number (D8065): 6506

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content: Using undefined instructions

Countermeasure: Please check if each instruction in the program is used correctly.

33, error number (D8065): 6507

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Wrong content: P number error

Countermeasure: Please check if each instruction in the program is used correctly.

34, error number (D8065): 6508

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content: I number error

Countermeasure: Please check if each instruction in the program is used correctly.

35, error number (D8065): 6509

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Wrong content: other

Countermeasure: Please check if each instruction in the program is used correctly.

36. Error number (D8065): 6510

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Wrong content: improper use of the N number of the MC/MCR

Countermeasure: Please check if each instruction in the program is used correctly.

37. Error number (D8065): 6511

Error message: SYNTAXERROR (PLC stopped running, grammar error)

Error content interrupt insertion input number and high-speed counter input number repeated use

Countermeasure: Please check if each instruction in the program is used correctly.