Using a network cable to return files from the touch screen to the computer, there is always a "pdz file not found", what is the cause? It has a wide range of applications, including power production and power dispatching center, nuclear industry facility operation center, energy production center, traffic operation monitoring center, aerospace mission monitoring center, public safety mission monitoring center, financial trading center, monitoring center, radio and television monitoring center, factory central control room and many other application scenarios. These types of control rooms, Both monitoring center and control center belong to mission critical control environment, which affects the orderly operation of economy and society.Operation method, installation and maintenance of jbkz tank liquid level alarm device. The device is applicable to the monitoring and alarm of high liquid level and overfill cargo tank. Oil Tanker Cargo Oil Console,Petrochemical Ship Cargo Oil Console,Oil Tank Monitoring Console,Tank Gauge Console Monitor Taizhou Jiabo Instrument Technology Co., Ltd. , https://www.taizhoujiabo.com
A: There are two necessary conditions for the touch screen return program -
1. When downloading the touch screen program, a memory card must be inserted on the touch screen;
2. Check "Enable Postback" when downloading the program.
The premise of the return is that your touch screen has a memory card (some touch screens do not support the memory card, it can not support the backhaul function), and your touch screen program was originally downloaded when the "Enable Backhaul" option was selected in the transfer settings. Two conditions are indispensable!
If both of the above are met, you will create a new project with the same device type and actual touch screen model. Set the communication port and protocol in "Project" - "Transfer" - "Transfer Settings".
If you can't return it, it is recommended that you use Prosave software to back up the mirror image of the touch screen, but the files obtained in this way cannot be opened and edited, and can only be used to download and restore the touch screen program.
If you have a return condition, the return steps are as follows -
1. First create a new project, the device type is the same as the actual touch screen model, and set the communication port and protocol in "Project" - "Transfer" - "Transfer Settings".
2. Select "Project" - "Transfer" - "Return".
The files returned by the above method can be opened and edited on the computer.
If you can't return the touch screen program without the return condition, you can only use the backup function to upload the touch screen program. The method is "project" - "transfer" - "backup", but the file thus obtained cannot be opened and edited. Can only be used to download and restore touch screen programs.